Traction converting substation from viewpoint of Freding interlocking plant at Czech Railways
Authors: Doleček Radovan | Dobrovolný Martin
Year: 2004
Type of publication: článek v odborném periodiku
Name of source: Advances in Electrical and Electronic Engineering
Publisher name: Vysoká škola báňská-Technická univerzita Ostrava
Place: Ostrava
Page from-to: 67-70
Titles:
Language Name Abstract Keywords
cze Trakční měnírna z pohledu napájení zabezpečovacího zařízení u ČD Substation, Traction transformer, Harmonic analysis, Resonance frequency
eng Traction converting substation from viewpoint of Freding interlocking plant at Czech Railways The paper presents analyses current and voltage harmonic in traction converting substation 3 kV. It researches their rise and influence to three-phase cable line 6 kV, 50 Hz that is used for feeding interlocking plant. Processing of this task is arisen from requirement practice for line Pěčky - Poříčany - Rostoklaty where happened to adverse ratio in particular transmission line of feeding system. It is meant especially about backward influence traction substation rectifier Pečky to three-phase cable line 6 kV, 50 Hz. At the determinate length of the cable line, when resonance frequency of circuit transformer 22 kV/ 6kV and the cable line 6 kV, 50 Hz is approached frequency 550 Hz and 650 Hz (i.e. 11 and 13 harmonic) are happened to so-called ?annulations input reactance of this circuit?. Substation, Traction transformer, Harmonic analysis, Resonance frequency